To request updates to the information shown, please email lee.barbi@epa.gov.


Instructions

The Air Monitoring Guidance tool has several options to show specific information. Use the tools below to find specific information:

  • Show By Chemical: Click the toggle to show the list of Compounds by Class, or unclick it to go back to the list by Response Types.
  • Response Types: Choose from one of the Response Types to show Compounds and Instruments for that Response Type.
  • Show Monitoring Only: By default, the list shows all instruments used for both monitoring and sampling. To show only monitoring tools, click "Show Monitoring Only."
  • Show/Hide Columns: Click to change the columns that are included in the list
  • Filters: Use the "Compound," "Class," or "Instrument" filters to review information for specific Compounds or Instruments.
  • Switch to Card View: Click "Switch to Card View" or "Switch to List View" to toggle between the "List" view or the "Card" view.

Caution! DRAFT ONLY

To verify the data presented in this tool, refer to the Agency for Toxic Substances and Disease Registry (ATSDR), EPA toxicologists, the National Institute of Occupational Safety and Health (NIOSH), the Occupational Safety and Health Administration (OSHA), device manufacturer handbooks (most are available online), equipment operating guides, and other authoritative regulatory guidance. More current data from any source used to compile these tables supersedes the information in these tables.

This document does not supersede the SSHASP for any response. During responses to unknown situations, use the most conservative criterion, approach, and personal protective equipment (PPE) as outlined in the SSHASP.

  • For responses involving metals in a particulate form, a particulate air monitoring instrument (e.g., TSI DustTrak) will provide real-time data. The instrumentation reading will be in total milligram per cubic meter (mg/m3) of particulate and not the metal of interest. Consult with a toxicologist or industrial hygienist for guidance in determining an action level.
  • When monitoring for combustible atmosphere, a combustible gas indicator (e.g., MultiRAE Pro) will need to be used. The action level for a combustible atmosphere is a lower explosive level (LEL) greater than 10%. A normal oxygen level in the ambient air should be between 19.5%-23.5% oxygen (normal 20.8%). An oxygen level below 19.5% or above 23.5% will require a reassessment of the situation. Teflon tubing is to be used for calibration instead of Tygon tubing for volatile organic compound analysis.
  • If you have any changes or revisions, please email: zintak.leonard@epa.gov

Show by Chemical

Response Types:

-1

Show Monitoring Only

  Compounds1 Resources Class Instruments Regulatory Info Air Sampling Instrument Intrinsically Safe Detection Level Used For Sampling IP PID ISO Conversion Commercial Residential TWA IDLH AEGL3
1 hr
AEGL
4 hr
AEGL
8 hr
PAC8
15 min
PAC8
1 hr
ERPG4 Level C Level B Media5 Method Flow Notes Compound Class: Compound: Instrument:

Hydrochloric Acid (Hydrogen Chloride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrochloric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-chloride)

Acids

AreaRAE HCl Sensor

  • AreaRAE HCl Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/arearae-pro)
  • Detection Level: 0-15 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-15 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
1.8 ppm
AEGL-1 4-hr:
1.8 ppm
AEGL-1 8-hr:
1.8 ppm
PAC-1 15-min (PAC):
1.8 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
3 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

AreaRAE HCl Sensor

Y 0-15 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 12.74 eV NA 1 ppm = 1.49 mg/m3 III NA NA PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm 50 ppm 1.8 ppm 1.8 ppm 1.8 ppm 1.8 ppm 3 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrochloric Acid (Hydrogen Ch AreaRAE HCl Sensor

Hydrochloric Acid (Hydrogen Chloride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrochloric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-chloride)

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
1.8 ppm
AEGL-1 4-hr:
1.8 ppm
AEGL-1 8-hr:
1.8 ppm
PAC-1 15-min (PAC):
1.8 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
3 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

Dräger Tube

Y 0.2-3 ppm,; 3-20 ppm
(Not Applicable)
No 12.74 eV NA 1 ppm = 1.49 mg/m3 III NA NA PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm 50 ppm 1.8 ppm 1.8 ppm 1.8 ppm 1.8 ppm 3 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrochloric Acid (Hydrogen Ch Dräger Tube

Hydrochloric Acid (Hydrogen Chloride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrochloric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-chloride)

Acids

Dräger Chip

Regulatory Info:

TWA:
PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
1.8 ppm
AEGL-1 4-hr:
1.8 ppm
AEGL-1 8-hr:
1.8 ppm
PAC-1 15-min (PAC):
1.8 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
3 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

Dräger Chip

Y ≥1-25 ppm
(Not Applicable)
No 12.74 eV NA 1 ppm = 1.49 mg/m3 III NA NA PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm 50 ppm 1.8 ppm 1.8 ppm 1.8 ppm 1.8 ppm 3 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrochloric Acid (Hydrogen Ch Dräger Chip

Hydrochloric Acid (Hydrogen Chloride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrochloric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-chloride)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
1.8 ppm
AEGL-1 4-hr:
1.8 ppm
AEGL-1 8-hr:
1.8 ppm
PAC-1 15-min (PAC):
1.8 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
3 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

pH Paper

Y 0-14
()
No 12.74 eV NA 1 ppm = 1.49 mg/m3 III NA NA PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm 50 ppm 1.8 ppm 1.8 ppm 1.8 ppm 1.8 ppm 3 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrochloric Acid (Hydrogen Ch pH Paper

Hydrochloric Acid (Hydrogen Chloride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrochloric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-chloride)

Acids

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.02-20 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.02-20 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
1.8 ppm
AEGL-1 4-hr:
1.8 ppm
AEGL-1 8-hr:
1.8 ppm
PAC-1 15-min (PAC):
1.8 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
3 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

SPM Flex

Y 0.02-20 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 12.74 eV NA 1 ppm = 1.49 mg/m3 III NA NA PEL = C 5 ppm; REL = C 5 ppm; TLV = C 2 ppm 50 ppm 1.8 ppm 1.8 ppm 1.8 ppm 1.8 ppm 3 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3, 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrochloric Acid (Hydrogen Ch SPM Flex

Nitric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Nitric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/nitric-acid)

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm
IDLH:
25 ppm
AEGL-1 1-hr:
0.16 ppm
AEGL-1 4-hr:
0.16 ppm
AEGL-1 8-hr:
0.16 ppm
PAC-1 15-min (PAC):
0.16 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
1 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

Dräger Tube

Y 1-15 ppm
(Not Applicable)
No 11.95 eV NA 1 ppm = 2.58 mg/m3 III NA NA PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm 25 ppm 0.16 ppm 0.16 ppm 0.16 ppm 0.16 ppm 1 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Nitric Acid Dräger Tube

Nitric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Nitric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/nitric-acid)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm
IDLH:
25 ppm
AEGL-1 1-hr:
0.16 ppm
AEGL-1 4-hr:
0.16 ppm
AEGL-1 8-hr:
0.16 ppm
PAC-1 15-min (PAC):
0.16 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
1 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

pH Paper

Y 0-14
()
No 11.95 eV NA 1 ppm = 2.58 mg/m3 III NA NA PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm 25 ppm 0.16 ppm 0.16 ppm 0.16 ppm 0.16 ppm 1 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Nitric Acid pH Paper

Nitric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Nitric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/nitric-acid)

Acids

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.02-20 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.02-20 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm
IDLH:
25 ppm
AEGL-1 1-hr:
0.16 ppm
AEGL-1 4-hr:
0.16 ppm
AEGL-1 8-hr:
0.16 ppm
PAC-1 15-min (PAC):
0.16 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
1 ppm

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

SPM Flex

Y 0.02-20 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 11.95 eV NA 1 ppm = 2.58 mg/m3 III NA NA PEL = 2 ppm; REL = 2 ppm, ST 4 ppm; TLV = 2 ppm, ST 4 ppm 25 ppm 0.16 ppm 0.16 ppm 0.16 ppm 0.16 ppm 1 ppm NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Nitric Acid SPM Flex

Sulfuric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfuric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/sulfuric-acid)

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3
IDLH:
15 mg/m3
AEGL-1 1-hr:
0.2 mg/m3
AEGL-1 4-hr:
0.2 mg/m3
AEGL-1 8-hr:
0.2 mg/m3
PAC-1 15-min (PAC):
0.2 mg/m3
PAC-1 1-hr:
ERPG-1 1-hr:
2 mg/m3

Air Sampling:

Media:
Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704
Method:
NIOSH 7908
Flow Rate/Total Volume:
1-5 L/min; 15-2000 L

Dräger Tube

Y 1-5 mg/m3
(Not Applicable)
No 12.4 eV NA NA III NA NA PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3 15 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 2 mg/m3 NA NA Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704 NIOSH 7908 1-5 L/min; 15-2000 L
Acids Sulfuric Acid Dräger Tube

Sulfuric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfuric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/sulfuric-acid)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3
IDLH:
15 mg/m3
AEGL-1 1-hr:
0.2 mg/m3
AEGL-1 4-hr:
0.2 mg/m3
AEGL-1 8-hr:
0.2 mg/m3
PAC-1 15-min (PAC):
0.2 mg/m3
PAC-1 1-hr:
ERPG-1 1-hr:
2 mg/m3

Air Sampling:

Media:
Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704
Method:
NIOSH 7908
Flow Rate/Total Volume:
1-5 L/min; 15-2000 L

pH Paper

Y 0-14
()
No 12.4 eV NA NA III NA NA PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3 15 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 2 mg/m3 NA NA Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704 NIOSH 7908 1-5 L/min; 15-2000 L
Acids Sulfuric Acid pH Paper

Sulfuric Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfuric%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/topics/sulfuric-acid)

Acids

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.005-0.75 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.005-0.75 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3
IDLH:
15 mg/m3
AEGL-1 1-hr:
0.2 mg/m3
AEGL-1 4-hr:
0.2 mg/m3
AEGL-1 8-hr:
0.2 mg/m3
PAC-1 15-min (PAC):
0.2 mg/m3
PAC-1 1-hr:
ERPG-1 1-hr:
2 mg/m3

Air Sampling:

Media:
Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704
Method:
NIOSH 7908
Flow Rate/Total Volume:
1-5 L/min; 15-2000 L

SPM Flex

Y 0.005-0.75 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 12.4 eV NA NA III NA NA PEL = 1 mg/m3; REL = 1 mg/m3; TLV = 0.2 mg/m3 15 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 0.2 mg/m3 2 mg/m3 NA NA Polytetrafluoroethylene (PTFE), 0.45 um pore size, 225-1704 NIOSH 7908 1-5 L/min; 15-2000 L
Acids Sulfuric Acid SPM Flex

Hydrocyanic Acid (Hydrogen Cyanide)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Cyanide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-cyanide)

Acids

MultiRAE/AreaRAE HCN Sensor

  • MultiRAE/AreaRAE HCN Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-50 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-50 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S
IDLH:
50 ppm
AEGL-1 1-hr:
2.0 ppm
AEGL-1 4-hr:
1.3 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube – soda lime and glass fiber filter, 226-28
Method:
NIOSH 6017
Flow Rate/Total Volume:
0.05-0.2 L/min; 2-90 L

MultiRAE/AreaRAE HCN Sensor

Y 0-50 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 13.6 eV NA 1 ppm = 1.1 mg/m3 III NA NA PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S 50 ppm 2.0 ppm 1.3 ppm 1 ppm 2 ppm NA NA NA Sorbent Tube – soda lime and glass fiber filter, 226-28 NIOSH 6017 0.05-0.2 L/min; 2-90 L
Acids Hydrocyanic Acid (Hydrogen Cya MultiRAE/AreaRAE HCN Sensor

Hydrocyanic Acid (Hydrogen Cyanide)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Cyanide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-cyanide)

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S
IDLH:
50 ppm
AEGL-1 1-hr:
2.0 ppm
AEGL-1 4-hr:
1.3 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube – soda lime and glass fiber filter, 226-28
Method:
NIOSH 6017
Flow Rate/Total Volume:
0.05-0.2 L/min; 2-90 L

Dräger Tube

Y 0.5-50 ppm, 5-50 ppm
(Not Applicable)
No 13.6 eV NA 1 ppm = 1.1 mg/m3 III NA NA PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S 50 ppm 2.0 ppm 1.3 ppm 1 ppm 2 ppm NA NA NA Sorbent Tube – soda lime and glass fiber filter, 226-28 NIOSH 6017 0.05-0.2 L/min; 2-90 L
Acids Hydrocyanic Acid (Hydrogen Cya Dräger Tube

Hydrocyanic Acid (Hydrogen Cyanide)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Cyanide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-cyanide)

Acids

Dräger Chip

Regulatory Info:

TWA:
PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S
IDLH:
50 ppm
AEGL-1 1-hr:
2.0 ppm
AEGL-1 4-hr:
1.3 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube – soda lime and glass fiber filter, 226-28
Method:
NIOSH 6017
Flow Rate/Total Volume:
0.05-0.2 L/min; 2-90 L

Dräger Chip

Y 2-50 ppm
(Not Applicable)
No 13.6 eV NA 1 ppm = 1.1 mg/m3 III NA NA PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S 50 ppm 2.0 ppm 1.3 ppm 1 ppm 2 ppm NA NA NA Sorbent Tube – soda lime and glass fiber filter, 226-28 NIOSH 6017 0.05-0.2 L/min; 2-90 L
Acids Hydrocyanic Acid (Hydrogen Cya Dräger Chip

Hydrocyanic Acid (Hydrogen Cyanide)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Cyanide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-cyanide)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S
IDLH:
50 ppm
AEGL-1 1-hr:
2.0 ppm
AEGL-1 4-hr:
1.3 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube – soda lime and glass fiber filter, 226-28
Method:
NIOSH 6017
Flow Rate/Total Volume:
0.05-0.2 L/min; 2-90 L

pH Paper

Y 0-14
()
No 13.6 eV NA 1 ppm = 1.1 mg/m3 III NA NA PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S 50 ppm 2.0 ppm 1.3 ppm 1 ppm 2 ppm NA NA NA Sorbent Tube – soda lime and glass fiber filter, 226-28 NIOSH 6017 0.05-0.2 L/min; 2-90 L
Acids Hydrocyanic Acid (Hydrogen Cya pH Paper

Hydrocyanic Acid (Hydrogen Cyanide)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Cyanide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogen-cyanide)

Acids

SPM

  • SPM Info (http://www.honeywellanalytics.com/~/media/honeywell-analytics/products/spm/documents/english/spm-_-technical-handbook-_-rev-10.pdf?la=en)
  • Quick Start Guide ( )
  • Detection Level: 0.2-30 ppm (http://www.honeywellanalytics.com/~/media/honeywell-analytics/products/spm/documents/english/spm-_-technical-handbook-_-rev-10.pdf?la=en)
  • Intrinsically Safe: Y (http://www.honeywellanalytics.com/~/media/honeywell-analytics/products/spm/documents/english/spm-_-technical-handbook-_-rev-10.pdf?la=en)
  • Used For Sampling: No
  • 0.2-30 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S
IDLH:
50 ppm
AEGL-1 1-hr:
2.0 ppm
AEGL-1 4-hr:
1.3 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube – soda lime and glass fiber filter, 226-28
Method:
NIOSH 6017
Flow Rate/Total Volume:
0.05-0.2 L/min; 2-90 L

SPM

Y 0.2-30 ppm
(http://www.honeywellanalytics.com/~/media/honeywell-analytics/products/spm/documents/english/spm-_-technical-handbook-_-rev-10.pdf?la=en)
No 13.6 eV NA 1 ppm = 1.1 mg/m3 III NA NA PEL = 10 ppm S; REL = ST 4.7 ppm S; TLV = 4.7 ppm S 50 ppm 2.0 ppm 1.3 ppm 1 ppm 2 ppm NA NA NA Sorbent Tube – soda lime and glass fiber filter, 226-28 NIOSH 6017 0.05-0.2 L/min; 2-90 L
Acids Hydrocyanic Acid (Hydrogen Cya SPM

Hydrofluoric Acid (Hydrogen Fluoride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrofluoric%20Acid)

Acids

AreaRAE HF Sensor

  • AreaRAE HF Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/arearae-pro)
  • Detection Level: 0.5-10 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0.5-10 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
2 ppm

Air Sampling:

Media:
Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031
Method:
NIOSH 7906
Flow Rate/Total Volume:
1-2 L/min; 15-1000 L

AreaRAE HF Sensor

Y 0.5-10 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 15.98 eV NA 1 ppm = 0.82 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm 2 ppm NA NA Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031 NIOSH 7906 1-2 L/min; 15-1000 L
Acids Hydrofluoric Acid (Hydrogen Fl AreaRAE HF Sensor

Hydrofluoric Acid (Hydrogen Fluoride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrofluoric%20Acid)

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
2 ppm

Air Sampling:

Media:
Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031
Method:
NIOSH 7906
Flow Rate/Total Volume:
1-2 L/min; 15-1000 L

Dräger Tube

Y 0.5-15 ppm,; 10-90 ppm
(Not Applicable)
No 15.98 eV NA 1 ppm = 0.82 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm 2 ppm NA NA Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031 NIOSH 7906 1-2 L/min; 15-1000 L
Acids Hydrofluoric Acid (Hydrogen Fl Dräger Tube

Hydrofluoric Acid (Hydrogen Fluoride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrofluoric%20Acid)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
2 ppm

Air Sampling:

Media:
Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031
Method:
NIOSH 7906
Flow Rate/Total Volume:
1-2 L/min; 15-1000 L

pH Paper

Y 0-14
()
No 15.98 eV NA 1 ppm = 0.82 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm 2 ppm NA NA Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031 NIOSH 7906 1-2 L/min; 15-1000 L
Acids Hydrofluoric Acid (Hydrogen Fl pH Paper

Hydrofluoric Acid (Hydrogen Fluoride)

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrofluoric%20Acid)

Acids

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.4-20 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.4-20 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
2 ppm

Air Sampling:

Media:
Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031
Method:
NIOSH 7906
Flow Rate/Total Volume:
1-2 L/min; 15-1000 L

SPM Flex

Y 0.4-20 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 15.98 eV NA 1 ppm = 0.82 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm, ST 6 ppm; TLV = C 2 ppm S, 0.5 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm 2 ppm NA NA Cartridge – two 37-mm diameter cellulose nitrate, one filter impregnated with NA2CO3, 225-9031 NIOSH 7906 1-2 L/min; 15-1000 L
Acids Hydrofluoric Acid (Hydrogen Fl SPM Flex

Hydrobromic Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrobromic%20Acid)

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm; TLV = C 2 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

pH Paper

Y 0-14
()
No 11.62 eV NA 1 ppm = 3.31 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm; TLV = C 2 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm NA NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrobromic Acid pH Paper

Hydrobromic Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrobromic%20Acid)

Acids

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.02-10 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.02-10 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 3 ppm; REL = C 3 ppm; TLV = C 2 ppm
IDLH:
30 ppm
AEGL-1 1-hr:
1 ppm
AEGL-1 4-hr:
1 ppm
AEGL-1 8-hr:
1 ppm
PAC-1 15-min (PAC):
1 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032
Method:
NIOSH 7907
Flow Rate/Total Volume:
2 L/min; 30-600 L

SPM Flex

Y 0.02-10 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 11.62 eV NA 1 ppm = 3.31 mg/m3 III NA NA PEL = 3 ppm; REL = C 3 ppm; TLV = C 2 ppm 30 ppm 1 ppm 1 ppm 1 ppm 1 ppm NA NA NA Cartridge - two 37-mm diameter quartz fiber filters, one filter impregnated with Na2CO3 225-9032 NIOSH 7907 2 L/min; 30-600 L
Acids Hydrobromic Acid SPM Flex

Acetic Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Acetic%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/npg/npgd0002.html )

Acids

Dräger Tube

Regulatory Info:

TWA:
PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
5 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
5 ppm

Air Sampling:

Media:
Sorbent Tube – charcoal 226-01
Method:
NIOSH 1603
Flow Rate/Total Volume:
0.01-1 L/min; 20-300 L

Dräger Tube

Y 5-80 ppm
(Not Applicable)
No 10.66 eV NA 1 ppm = 2.46 mg/m3 III NA NA PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm 50 ppm NA NA NA 5 ppm 5 ppm NA NA Sorbent Tube – charcoal 226-01 NIOSH 1603 0.01-1 L/min; 20-300 L
Acids Acetic Acid Dräger Tube

Acetic Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Acetic%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/npg/npgd0002.html )

Acids

Dräger Chip

Regulatory Info:

TWA:
PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
5 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
5 ppm

Air Sampling:

Media:
Sorbent Tube – charcoal 226-01
Method:
NIOSH 1603
Flow Rate/Total Volume:
0.01-1 L/min; 20-300 L

Dräger Chip

Y 2-50 ppm
(Not Applicable)
No 10.66 eV NA 1 ppm = 2.46 mg/m3 III NA NA PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm 50 ppm NA NA NA 5 ppm 5 ppm NA NA Sorbent Tube – charcoal 226-01 NIOSH 1603 0.01-1 L/min; 20-300 L
Acids Acetic Acid Dräger Chip

Acetic Acid

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Acetic%20Acid)
  • NIOSH (https://www.cdc.gov/niosh/npg/npgd0002.html )

Acids

pH Paper

Regulatory Info:

TWA:
PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm
IDLH:
50 ppm
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
5 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
5 ppm

Air Sampling:

Media:
Sorbent Tube – charcoal 226-01
Method:
NIOSH 1603
Flow Rate/Total Volume:
0.01-1 L/min; 20-300 L

pH Paper

Y 0-14
()
No 10.66 eV NA 1 ppm = 2.46 mg/m3 III NA NA PEL = 10 ppm; REL = 10 ppm, ST 15 ppm; TLV = 10 ppm, ST 15 ppm 50 ppm NA NA NA 5 ppm 5 ppm NA NA Sorbent Tube – charcoal 226-01 NIOSH 1603 0.01-1 L/min; 20-300 L
Acids Acetic Acid pH Paper

Oxygen

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Oxygen)

Gases

MultiRAE/AreaRAE O2 Sensor

  • MultiRAE/AreaRAE O2 Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-30% Vol. (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-30% Vol.
  • PID CF ISO: NA

Regulatory Info:

TWA:
<19.5% O2 (simple asphyxiant)
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
NA
Method:
NA
Flow Rate/Total Volume:
NA

MultiRAE/AreaRAE O2 Sensor

Y 0-30% Vol.
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 12.35 eV NA NA III NA NA <19.5% O2 (simple asphyxiant) NA NA NA NA NA NA NA NA NA NA NA
Gases Oxygen MultiRAE/AreaRAE O2 Sensor

Oxygen

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Oxygen)

Gases

Dräger Tube

Regulatory Info:

TWA:
<19.5% O2 (simple asphyxiant)
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
NA
Method:
NA
Flow Rate/Total Volume:
NA

Dräger Tube

Y 5-23% Vol.
(Not Applicable)
No 12.35 eV NA NA III NA NA <19.5% O2 (simple asphyxiant) NA NA NA NA NA NA NA NA NA NA NA
Gases Oxygen Dräger Tube

Oxygen

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Oxygen)

Gases

Dräger Chip

Regulatory Info:

TWA:
<19.5% O2 (simple asphyxiant)
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
NA
Method:
NA
Flow Rate/Total Volume:
NA

Dräger Chip

Y 1-30% Vol.
(Not Applicable)
No 12.35 eV NA NA III NA NA <19.5% O2 (simple asphyxiant) NA NA NA NA NA NA NA NA NA NA NA
Gases Oxygen Dräger Chip

Hydrogen

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen)

Gases

Dräger Tube

Regulatory Info:

TWA:
<19.5% O2 (simple asphyxiant)
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
NA
Method:
NA
Flow Rate/Total Volume:
NA

Dräger Tube

Y 0.2-2% Vol.
(Not Applicable)
No 15.42 eV NA NA III NA NA <19.5% O2 (simple asphyxiant) NA NA NA NA NA NA NA NA NA NA NA
Ionization potential value not availble in the NIOSH pocket guide to chemical hazards. IP information from the Nastional Institute of Standards and Technology.
Gases Hydrogen Dräger Tube

Radiation 2

Resources:

Particulates and Radiation

Model 192 Micro R Exposure Rate Meter

Regulatory Info:

TWA:
10 µR/hr
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Model 192 Micro R Exposure Rate Meter

N 0-5,000 µR/hr
(https://ludlums.com/images/product_manuals/M192.pdf)
No NA NA NA III NA NA 10 µR/hr NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Model 192 Micro R Exposure Rat

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241-2 w/ 44-9 Pancake Probe

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241-2 w/ 44-9 Pancake Probe

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241-2.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241-2 w/ 44-9 Pa

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241-3 w/ 44-9 Pancake Probe

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241-3 w/ 44-9 Pancake Probe

N 0-9,999 R/hr or 999,000 cpm
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241-3 w/ 44-9 Pa

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241 w/ 43-90 Alpha Scintillator

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241 w/ 43-90 Alpha Scintillator

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241 w/ 43-90 Alp

Radiation 2

Resources:

Particulates and Radiation

Model 2241 w/ Model 44-10 Nal Detector

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Model 2241 w/ Model 44-10 Nal Detector

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Model 2241 w/ Model 44-10 Nal

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

AreaRAE NH3 Sensor

  • AreaRAE NH3 Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/arearae-pro)
  • Detection Level: 0-100 ppm; (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-100 ppm;
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

AreaRAE NH3 Sensor

Y 0-100 ppm;
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 10.18 eV NA 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
Gases Ammonia AreaRAE NH3 Sensor

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

MultiRAE Pro NH3 Sensor

  • MultiRAE Pro NH3 Sensor Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/Quick_Start_MultiRAE2_QuickStart_Guide_Pumped_RevC_English.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/multirae-pro)
  • Detection Level: 0-100 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Used For Sampling: No
  • 0-100 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

MultiRAE Pro NH3 Sensor

Y 0-100 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
No 10.18 eV NA 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
Gases Ammonia MultiRAE Pro NH3 Sensor

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

Dräger Tube

Y 2-30 ppm
(Not Applicable)
No 10.18 eV NA 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
Gases Ammonia Dräger Tube

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

Dräger Chip

Y 2-50 ppm
(Not Applicable)
No 10.18 eV NA 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
Gases Ammonia Dräger Chip

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.01-150 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.01-150 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

SPM Flex

Y 0.01-150 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 10.18 eV NA 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
Gases Ammonia SPM Flex

Ammonia

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Ammonia)
  • NIOSH (https://www.cdc.gov/niosh/topics/Ammonia)

Gases

MultiRAE/AreaRAE PID

  • MultiRAE/AreaRAE PID Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-2000 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-2000 ppm
  • PID CF ISO: 10.6 lamp, 10.9; 11.7 lamp, 5.7

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm
IDLH:
300 ppm
AEGL-1 1-hr:
30 ppm
AEGL-1 4-hr:
30 ppm
AEGL-1 8-hr:
30 ppm
PAC-1 15-min (PAC):
30 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
25 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, 226-10-06
Method:
NIOSH 6015, NIOSH 6016
Flow Rate/Total Volume:
0.1-0.2 L/min; 96 L max

MultiRAE/AreaRAE PID

Y 0-2000 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 10.18 eV 10.6 lamp, 10.9; 11.7 lamp, 5.7 1 ppm = 0.7 mg/m3 III NA NA PEL = 50 ppm; REL = 25 ppm, ST 35 ppm; TLV = 25 ppm, ST 35 ppm 300 ppm 30 ppm 30 ppm 30 ppm 30 ppm 25 ppm NA NA Sorbent Tube, Silica Gel, 226-10-06 NIOSH 6015, NIOSH 6016 0.1-0.2 L/min; 96 L max
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information.
Gases Ammonia MultiRAE/AreaRAE PID

Radiation 2

Resources:

Particulates and Radiation

Model 192 Micro R Exposure Rate Meter

Regulatory Info:

TWA:
10 µR/hr
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Model 192 Micro R Exposure Rate Meter

N 0-5,000 µR/hr
(https://ludlums.com/images/product_manuals/M192.pdf)
No NA NA NA III NA NA 10 µR/hr NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Model 192 Micro R Exposure Rat

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241-2 w/ 44-9 Pancake Probe

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241-2 w/ 44-9 Pancake Probe

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241-2.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241-2 w/ 44-9 Pa

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241-3 w/ 44-9 Pancake Probe

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241-3 w/ 44-9 Pancake Probe

N 0-9,999 R/hr or 999,000 cpm
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241-3 w/ 44-9 Pa

Radiation 2

Resources:

Particulates and Radiation

Ludlum Model 2241 w/ 43-90 Alpha Scintillator

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Ludlum Model 2241 w/ 43-90 Alpha Scintillator

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Ludlum Model 2241 w/ 43-90 Alp

Radiation 2

Resources:

Particulates and Radiation

Model 2241 w/ Model 44-10 Nal Detector

Regulatory Info:

TWA:
300 cpm
IDLH:
NA
AEGL-1 1-hr:
NA
AEGL-1 4-hr:
NA
AEGL-1 8-hr:
NA
PAC-1 15-min (PAC):
NA
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
RADeCO Filter Paper (2")
Method:
RSSOP 209/501
Flow Rate/Total Volume:
α = 2500 ft3 β/ϒ = 1250 ft3

Model 2241 w/ Model 44-10 Nal Detector

N 0-9,999 R/hr or 999,000 cpm
(https://ludlums.com/images/product_manuals/M2241.pdf)
No NA NA NA III NA NA 300 cpm NA NA NA NA NA NA NA NA RADeCO Filter Paper (2") RSSOP 209/501 α = 2500 ft3 β/ϒ = 1250 ft3
Particulates and Radiation Radiation Model 2241 w/ Model 44-10 Nal

Benzene

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Benzene)
  • NIOSH (https://www.cdc.gov/niosh/topics/Benzene)

VOCs and Gases

UltraRAE PGM-7360

  • UltraRAE PGM-7360 Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/Quick-Start_3GPID_RevA_English_0.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/ultrarae-3000)
  • Detection Level: 0.05-200 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Used For Sampling: No
  • 0.05-200 ppm
  • PID CF ISO: 9.8 lamp, 0.55

Regulatory Info:

TWA:
PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm
IDLH:
500 ppm
AEGL-1 1-hr:
52 ppm
AEGL-1 4-hr:
18 ppm
AEGL-1 8-hr:
9 ppm
PAC-1 15-min (PAC):
52 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
50 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag
Method:
NIOSH 1501 TO-15 TO-3
Flow Rate/Total Volume:
≤0.2 L/min; 5-30 L ≤200 mL/min

UltraRAE PGM-7360

Y 0.05-200 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
No 9.24 eV 9.8 lamp, 0.55 1 ppm = 3.19 mg/m3 III NA NA PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm 500 ppm 52 ppm 18 ppm 9 ppm 52 ppm 50 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag NIOSH 1501 TO-15 TO-3 ≤0.2 L/min; 5-30 L ≤200 mL/min
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information. Calibrate TVA 2020 with 100-500 ppm methane for accurate results from 1-10.000 ppm.
VOCs and Gases Benzene UltraRAE PGM-7360

Benzene

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Benzene)
  • NIOSH (https://www.cdc.gov/niosh/topics/Benzene)

VOCs and Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm
IDLH:
500 ppm
AEGL-1 1-hr:
52 ppm
AEGL-1 4-hr:
18 ppm
AEGL-1 8-hr:
9 ppm
PAC-1 15-min (PAC):
52 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
50 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag
Method:
NIOSH 1501 TO-15 TO-3
Flow Rate/Total Volume:
≤0.2 L/min; 5-30 L ≤200 mL/min

Dräger Tube

Y 0.25-2 ppm, 2-10 ppm
(Not Applicable)
No 9.24 eV NA 1 ppm = 3.19 mg/m3 III NA NA PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm 500 ppm 52 ppm 18 ppm 9 ppm 52 ppm 50 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag NIOSH 1501 TO-15 TO-3 ≤0.2 L/min; 5-30 L ≤200 mL/min
VOCs and Gases Benzene Dräger Tube

Benzene

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Benzene)
  • NIOSH (https://www.cdc.gov/niosh/topics/Benzene)

VOCs and Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm
IDLH:
500 ppm
AEGL-1 1-hr:
52 ppm
AEGL-1 4-hr:
18 ppm
AEGL-1 8-hr:
9 ppm
PAC-1 15-min (PAC):
52 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
50 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag
Method:
NIOSH 1501 TO-15 TO-3
Flow Rate/Total Volume:
≤0.2 L/min; 5-30 L ≤200 mL/min

Dräger Chip

Y 0.2-10 ppm
(Not Applicable)
No 9.24 eV NA 1 ppm = 3.19 mg/m3 III NA NA PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm 500 ppm 52 ppm 18 ppm 9 ppm 52 ppm 50 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag NIOSH 1501 TO-15 TO-3 ≤0.2 L/min; 5-30 L ≤200 mL/min
VOCs and Gases Benzene Dräger Chip

Benzene

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Benzene)
  • NIOSH (https://www.cdc.gov/niosh/topics/Benzene)

VOCs and Gases

MultiRAE/AreaRAE PID

  • MultiRAE/AreaRAE PID Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-2000 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-2000 ppm
  • PID CF ISO: 10.6 lamp, 0.47

Regulatory Info:

TWA:
PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm
IDLH:
500 ppm
AEGL-1 1-hr:
52 ppm
AEGL-1 4-hr:
18 ppm
AEGL-1 8-hr:
9 ppm
PAC-1 15-min (PAC):
52 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
50 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag
Method:
NIOSH 1501 TO-15 TO-3
Flow Rate/Total Volume:
≤0.2 L/min; 5-30 L ≤200 mL/min

MultiRAE/AreaRAE PID

Y 0-2000 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 9.24 eV 10.6 lamp, 0.47 1 ppm = 3.19 mg/m3 III NA NA PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm 500 ppm 52 ppm 18 ppm 9 ppm 52 ppm 50 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag NIOSH 1501 TO-15 TO-3 ≤0.2 L/min; 5-30 L ≤200 mL/min
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information. Calibrate TVA 2020 with 100-500 ppm methane for accurate results from 1-10.000 ppm.
VOCs and Gases Benzene MultiRAE/AreaRAE PID

Benzene

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Benzene)
  • NIOSH (https://www.cdc.gov/niosh/topics/Benzene)

VOCs and Gases

TVA 2020

  • TVA 2020 Info (https://www.thermofisher.com/document-connect/document-connect.html?url=https://assets.thermofisher.com/TFS-Assets%2FLSG%2Fmanuals%2FEPM-manual-TVA2020.pdf)
  • (https://www.thermofisher.com/order/catalog/product/TVA2020)
  • Detection Level: 0.5-2,000 ppm (PID); 1-10,000 ppm (FID) (https://assets.thermofisher.com/TFS-Assets/LSG/manuals/EPM-manual-TVA2020.pdf)
  • Intrinsically Safe: Y (https://www.thermofisher.com/order/catalog/product/TVA2020)
  • Used For Sampling: No
  • 0.5-2,000 ppm (PID); 1-10,000 ppm (FID)
  • PID CF ISO: 10.6 lamp; 0.294 (10 ppm) - 0.282 (1000 ppm)

Regulatory Info:

TWA:
PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm
IDLH:
500 ppm
AEGL-1 1-hr:
52 ppm
AEGL-1 4-hr:
18 ppm
AEGL-1 8-hr:
9 ppm
PAC-1 15-min (PAC):
52 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
50 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag
Method:
NIOSH 1501 TO-15 TO-3
Flow Rate/Total Volume:
≤0.2 L/min; 5-30 L ≤200 mL/min

TVA 2020

Y 0.5-2,000 ppm (PID); 1-10,000 ppm (FID)
(https://assets.thermofisher.com/TFS-Assets/LSG/manuals/EPM-manual-TVA2020.pdf)
No 9.24 eV 10.6 lamp; 0.294 (10 ppm) - 0.282 (1000 ppm) 1 ppm = 3.19 mg/m3 III NA NA PEL = 1 ppm, ST 5 pm; REL = 0.1 ppm, ST 1 ppm; TLV = 0.5 ppm, ST 2.5 ppm 500 ppm 52 ppm 18 ppm 9 ppm 52 ppm 50 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01/Summa Canister/Tedlar bag NIOSH 1501 TO-15 TO-3 ≤0.2 L/min; 5-30 L ≤200 mL/min
VOCs and Gases Benzene TVA 2020

Carbon Monoxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Carbon%20Monoxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/co-comp/ )

VOCs and Gases

MultiRAE/AreaRAE CO Sensor

  • MultiRAE/AreaRAE CO Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-500 ppm, 0-2000 ppm ext range (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-500 ppm, 0-2000 ppm ext range
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm
IDLH:
1200 ppm
AEGL-1 1-hr:
83 ppm
AEGL-1 4-hr:
33 ppm
AEGL-1 8-hr:
27 ppm
PAC-1 15-min (PAC):
75 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
200 ppm

Air Sampling:

Media:
Five-layer aluminized gas sampling bag, 262-01
Method:
OSHA ID 210
Flow Rate/Total Volume:
1 L/min, 2-5 L

MultiRAE/AreaRAE CO Sensor

Y 0-500 ppm, 0-2000 ppm ext range
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 14.01 eV NA 1 ppm = 1.15 mg/m3 III NA NA PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm 1200 ppm 83 ppm 33 ppm 27 ppm 75 ppm 200 ppm NA NA Five-layer aluminized gas sampling bag, 262-01 OSHA ID 210 1 L/min, 2-5 L
AEGL-2--There are no AEGL-1 for this compound.
AEGL-2 is the airborne concentration of a substance above which it is predicted that the general population, including susceptible individuals, could experience irreversible or other serious, long-lasting adverse health effects or an impaired ability to escape.
VOCs and Gases Carbon Monoxide MultiRAE/AreaRAE CO Sensor

Carbon Monoxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Carbon%20Monoxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/co-comp/ )

VOCs and Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm
IDLH:
1200 ppm
AEGL-1 1-hr:
83 ppm
AEGL-1 4-hr:
33 ppm
AEGL-1 8-hr:
27 ppm
PAC-1 15-min (PAC):
75 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
200 ppm

Air Sampling:

Media:
Five-layer aluminized gas sampling bag, 262-01
Method:
OSHA ID 210
Flow Rate/Total Volume:
1 L/min, 2-5 L

Dräger Tube

Y 5- 150 ppm, 100-700 ppm
(Not Applicable)
No 14.01 eV NA 1 ppm = 1.15 mg/m3 III NA NA PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm 1200 ppm 83 ppm 33 ppm 27 ppm 75 ppm 200 ppm NA NA Five-layer aluminized gas sampling bag, 262-01 OSHA ID 210 1 L/min, 2-5 L
AEGL-2--There are no AEGL-1 for this compound.
AEGL-2 is the airborne concentration of a substance above which it is predicted that the general population, including susceptible individuals, could experience irreversible or other serious, long-lasting adverse health effects or an impaired ability to escape.
VOCs and Gases Carbon Monoxide Dräger Tube

Carbon Monoxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Carbon%20Monoxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/co-comp/ )

VOCs and Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm
IDLH:
1200 ppm
AEGL-1 1-hr:
83 ppm
AEGL-1 4-hr:
33 ppm
AEGL-1 8-hr:
27 ppm
PAC-1 15-min (PAC):
75 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
200 ppm

Air Sampling:

Media:
Five-layer aluminized gas sampling bag, 262-01
Method:
OSHA ID 210
Flow Rate/Total Volume:
1 L/min, 2-5 L

Dräger Chip

Y 5-150 ppm
(Not Applicable)
No 14.01 eV NA 1 ppm = 1.15 mg/m3 III NA NA PEL = 50 ppm; REL = 35 ppm, C 200 ppm; TLV = 25 ppm 1200 ppm 83 ppm 33 ppm 27 ppm 75 ppm 200 ppm NA NA Five-layer aluminized gas sampling bag, 262-01 OSHA ID 210 1 L/min, 2-5 L
AEGL-2--There are no AEGL-1 for this compound.
AEGL-2 is the airborne concentration of a substance above which it is predicted that the general population, including susceptible individuals, could experience irreversible or other serious, long-lasting adverse health effects or an impaired ability to escape.
VOCs and Gases Carbon Monoxide Dräger Chip

Hydrogen Sulfide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Sulfide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogensulfide)

VOCs and Gases

MultiRAE/AreaRAE H2S Sensor

  • MultiRAE/AreaRAE H2S Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-100 ppm, 0-1000 ppm ext. range (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-100 ppm, 0-1000 ppm ext. range
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.51 ppm
AEGL-1 4-hr:
0.36 ppm
AEGL-1 8-hr:
0.33 ppm
PAC-1 15-min (PAC):
0.51 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.1 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177
Method:
OSHA 1008 NIOSH 6013
Flow Rate/Total Volume:
0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L

MultiRAE/AreaRAE H2S Sensor

Y 0-100 ppm, 0-1000 ppm ext. range
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 10.46 eV NA 1 ppm = 1.4 mg/m3 III NA NA PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm 100 ppm 0.51 ppm 0.36 ppm 0.33 ppm 0.51 ppm 0.1 ppm NA NA Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177 OSHA 1008 NIOSH 6013 0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L
VOCs and Gases Hydrogen Sulfide MultiRAE/AreaRAE H2S Sensor

Hydrogen Sulfide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Sulfide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogensulfide)

VOCs and Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.51 ppm
AEGL-1 4-hr:
0.36 ppm
AEGL-1 8-hr:
0.33 ppm
PAC-1 15-min (PAC):
0.51 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.1 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177
Method:
OSHA 1008 NIOSH 6013
Flow Rate/Total Volume:
0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L

Dräger Tube

Y ≥0.2-6 ppm
(Not Applicable)
No 10.46 eV NA 1 ppm = 1.4 mg/m3 III NA NA PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm 100 ppm 0.51 ppm 0.36 ppm 0.33 ppm 0.51 ppm 0.1 ppm NA NA Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177 OSHA 1008 NIOSH 6013 0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L
VOCs and Gases Hydrogen Sulfide Dräger Tube

Hydrogen Sulfide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Sulfide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogensulfide)

VOCs and Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.51 ppm
AEGL-1 4-hr:
0.36 ppm
AEGL-1 8-hr:
0.33 ppm
PAC-1 15-min (PAC):
0.51 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.1 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177
Method:
OSHA 1008 NIOSH 6013
Flow Rate/Total Volume:
0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L

Dräger Chip

Y ≥0.2-5 ppm
(Not Applicable)
No 10.46 eV NA 1 ppm = 1.4 mg/m3 III NA NA PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm 100 ppm 0.51 ppm 0.36 ppm 0.33 ppm 0.51 ppm 0.1 ppm NA NA Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177 OSHA 1008 NIOSH 6013 0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L
VOCs and Gases Hydrogen Sulfide Dräger Chip

Hydrogen Sulfide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Sulfide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogensulfide)

VOCs and Gases

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.001-9.999 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.001-9.999 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.51 ppm
AEGL-1 4-hr:
0.36 ppm
AEGL-1 8-hr:
0.33 ppm
PAC-1 15-min (PAC):
0.51 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.1 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177
Method:
OSHA 1008 NIOSH 6013
Flow Rate/Total Volume:
0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L

SPM Flex

Y 0.001-9.999 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 10.46 eV NA 1 ppm = 1.4 mg/m3 III NA NA PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm 100 ppm 0.51 ppm 0.36 ppm 0.33 ppm 0.51 ppm 0.1 ppm NA NA Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177 OSHA 1008 NIOSH 6013 0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L
VOCs and Gases Hydrogen Sulfide SPM Flex

Hydrogen Sulfide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Hydrogen%20Sulfide)
  • NIOSH (https://www.cdc.gov/niosh/topics/hydrogensulfide)

VOCs and Gases

MultiRAE/AreaRAE PID

  • MultiRAE/AreaRAE PID Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-2000 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-2000 ppm
  • PID CF ISO: 10.6 lamp, 3.3

Regulatory Info:

TWA:
PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.51 ppm
AEGL-1 4-hr:
0.36 ppm
AEGL-1 8-hr:
0.33 ppm
PAC-1 15-min (PAC):
0.51 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.1 ppm

Air Sampling:

Media:
Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177
Method:
OSHA 1008 NIOSH 6013
Flow Rate/Total Volume:
0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L

MultiRAE/AreaRAE PID

Y 0-2000 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 10.46 eV 10.6 lamp, 3.3 1 ppm = 1.4 mg/m3 III NA NA PEL = C 20 ppm, 50 ppm (10 mins); REL = C 10 ppm (10 mins); TLV = 1 ppm, ST 5 ppm 100 ppm 0.51 ppm 0.36 ppm 0.33 ppm 0.51 ppm 0.1 ppm NA NA Sorbent Tube, Silica Gel, For Hydrogen Sulfide, Sulfur Dioxide, 266-177 OSHA 1008 NIOSH 6013 0.05 L/min; 12 L 0.1 to 1.5 L/min (0.2 L/min rec); 1.2-40 L
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information. Calibrate TVA 2020 with 100-500 ppm methane for accurate results from 1-10.000 ppm.
VOCs and Gases Hydrogen Sulfide MultiRAE/AreaRAE PID

Sulfur Dioxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfur%20Dioxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/SulfurDioxide)

VOCs and Gases

MultiRAE/AreaRAE SO2 Sensor

  • MultiRAE/AreaRAE SO2 Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-20 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-20 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.2 ppm
AEGL-1 4-hr:
0.2 ppm
AEGL-1 8-hr:
0.2 ppm
PAC-1 15-min (PAC):
0.2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.3 ppm

Air Sampling:

Media:
Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005
Method:
NIOSH 6004
Flow Rate/Total Volume:
0.5-1.5 L/min; 4-200 L

MultiRAE/AreaRAE SO2 Sensor

Y 0-20 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 12.3 eV NA 1 ppm = 2.62 mg/m3 III NA NA PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm 100 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.3 ppm NA NA Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005 NIOSH 6004 0.5-1.5 L/min; 4-200 L
VOCs and Gases Sulfur Dioxide MultiRAE/AreaRAE SO2 Sensor

Sulfur Dioxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfur%20Dioxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/SulfurDioxide)

VOCs and Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.2 ppm
AEGL-1 4-hr:
0.2 ppm
AEGL-1 8-hr:
0.2 ppm
PAC-1 15-min (PAC):
0.2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.3 ppm

Air Sampling:

Media:
Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005
Method:
NIOSH 6004
Flow Rate/Total Volume:
0.5-1.5 L/min; 4-200 L

Dräger Tube

Y ≥0.1-3 ppm
(Not Applicable)
No 12.3 eV NA 1 ppm = 2.62 mg/m3 III NA NA PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm 100 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.3 ppm NA NA Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005 NIOSH 6004 0.5-1.5 L/min; 4-200 L
VOCs and Gases Sulfur Dioxide Dräger Tube

Sulfur Dioxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfur%20Dioxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/SulfurDioxide)

VOCs and Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.2 ppm
AEGL-1 4-hr:
0.2 ppm
AEGL-1 8-hr:
0.2 ppm
PAC-1 15-min (PAC):
0.2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.3 ppm

Air Sampling:

Media:
Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005
Method:
NIOSH 6004
Flow Rate/Total Volume:
0.5-1.5 L/min; 4-200 L

Dräger Chip

Y ≥0.4-10 ppm
(Not Applicable)
No 12.3 eV NA 1 ppm = 2.62 mg/m3 III NA NA PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm 100 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.3 ppm NA NA Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005 NIOSH 6004 0.5-1.5 L/min; 4-200 L
VOCs and Gases Sulfur Dioxide Dräger Chip

Sulfur Dioxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Sulfur%20Dioxide)
  • NIOSH (https://www.cdc.gov/niosh/topics/SulfurDioxide)

VOCs and Gases

SPM Flex

  • SPM Flex Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/high-tech-and-semiconductor/spm-flex/sps-his-spm-flex-qsg-eng-rev-4-v2.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/high-tech-and-semiconductor/spm-flex)
  • Detection Level: 0.01-2.5 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
  • Used For Sampling: No
  • 0.01-2.5 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
0.2 ppm
AEGL-1 4-hr:
0.2 ppm
AEGL-1 8-hr:
0.2 ppm
PAC-1 15-min (PAC):
0.2 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
0.3 ppm

Air Sampling:

Media:
Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005
Method:
NIOSH 6004
Flow Rate/Total Volume:
0.5-1.5 L/min; 4-200 L

SPM Flex

Y 0.01-2.5 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/industrial-fixed/spm-flex/sps-his-spm-flex-user-manual-eng-rev-09.pdf?download=false)
No 12.3 eV NA 1 ppm = 2.62 mg/m3 III NA NA PEL = 5 ppm; REL = 2 ppm, ST 5 ppm; TLV = ST 0.25 ppm 100 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.2 ppm 0.3 ppm NA NA Preloaded Cassette, MCE, Coated, Sodium Carbonate, 225-9005 NIOSH 6004 0.5-1.5 L/min; 4-200 L
VOCs and Gases Sulfur Dioxide SPM Flex

Nitric Oxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Nitric%20Oxide)

VOCs and Gases

UltraRAE PGM-7360

  • UltraRAE PGM-7360 Info (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/Quick-Start_3GPID_RevA_English_0.pdf?download=false)
  • (https://sps.honeywell.com/us/en/products/safety/gas-and-flame-detection/portables/ultrarae-3000)
  • Detection Level: 0.05-10000 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
  • Used For Sampling: No
  • 0.05-10000 ppm
  • PID CF ISO: 9.8 lamp, 6

Regulatory Info:

TWA:
PEL = 25 ppm; REL = 25 ppm; TLV = 25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
NR
AEGL-1 4-hr:
NR
AEGL-1 8-hr:
NR
PAC-1 15-min (PAC):
0.5 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube, Molecular Sieve, 226-40
Method:
NIOSH 6014
Flow Rate/Total Volume:
0.025 L/min; 1.5-6 L

UltraRAE PGM-7360

Y 0.05-10000 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/sps-his-3g-pid-user-s-guide-rev-b.pdf?download=false)
No 9.27 eV 9.8 lamp, 6 1 ppm = 1.23 mg/m3 III NA NA PEL = 25 ppm; REL = 25 ppm; TLV = 25 ppm 100 ppm NR NR NR 0.5 ppm NA NA NA Sorbent Tube, Molecular Sieve, 226-40 NIOSH 6014 0.025 L/min; 1.5-6 L
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information. Calibrate TVA 2020 with 100-500 ppm methane for accurate results from 1-10.000 ppm.
VOCs and Gases Nitric Oxide UltraRAE PGM-7360

Nitric Oxide

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Nitric%20Oxide)

VOCs and Gases

MultiRAE/AreaRAE NO Sensor

  • MultiRAE/AreaRAE NO Sensor Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-250 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-250 ppm
  • PID CF ISO: NA

Regulatory Info:

TWA:
PEL = 25 ppm; REL = 25 ppm; TLV = 25 ppm
IDLH:
100 ppm
AEGL-1 1-hr:
NR
AEGL-1 4-hr:
NR
AEGL-1 8-hr:
NR
PAC-1 15-min (PAC):
0.5 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
NA

Air Sampling:

Media:
Sorbent Tube, Molecular Sieve, 226-40
Method:
NIOSH 6014
Flow Rate/Total Volume:
0.025 L/min; 1.5-6 L

MultiRAE/AreaRAE NO Sensor

Y 0-250 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 9.27 eV NA 1 ppm = 1.23 mg/m3 III NA NA PEL = 25 ppm; REL = 25 ppm; TLV = 25 ppm 100 ppm NR NR NR 0.5 ppm NA NA NA Sorbent Tube, Molecular Sieve, 226-40 NIOSH 6014 0.025 L/min; 1.5-6 L
VOCs and Gases Nitric Oxide MultiRAE/AreaRAE NO Sensor

Vinyl Chloride

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Vinyl%20Chloride)

VOCs and Gases

MultiRAE/AreaRAE PID

  • MultiRAE/AreaRAE PID Info (https://sps.honeywell.com/content/dam/his-sandbox/products/gas-and-flame-detection/documents/AreaRAE2_UsersGuide_Rev_B.pdf)
  • Quick Start Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-w01-4012-000-revc-arearae2-quickstart-guide-en.pdf?download=false)
  • MultiRae User Guide (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/MultiRAE_UsersGuide_Rev_J_EN.pdf?download=false)
  • Detection Level: 0-2000 ppm (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Intrinsically Safe: Y (https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
  • Used For Sampling: No
  • 0-2000 ppm
  • PID CF ISO: 10.6 lamp, 2

Regulatory Info:

TWA:
PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm
IDLH:
NA
AEGL-1 1-hr:
250 ppm
AEGL-1 4-hr:
140 ppm
AEGL-1 8-hr:
70 ppm
PAC-1 15-min (PAC):
250 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
500 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag
Method:
NIOSH 1007/TO 15
Flow Rate/Total Volume:
0.05 L/min; <200mL/min (6L Summa); 0.7-5 L

MultiRAE/AreaRAE PID

Y 0-2000 ppm
(https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/his/en-us/products/gas-and-flame-detection/documents/arearae/sps-his-arearae2-usersguide-rev-c.pdf?download=false)
No 9.99 eV 10.6 lamp, 2 1 ppm = 2.56 mg/m3 III NA NA PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm NA 250 ppm 140 ppm 70 ppm 250 ppm 500 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag NIOSH 1007/TO 15 0.05 L/min; <200mL/min (6L Summa); 0.7-5 L
PIDs and FIDs are non-specific detectors and cannot differentiate one VOC from another, even with CFs applied. See RAE PID Correction factor guidance document TN-106 for more information. Calibrate TVA 2020 with 100-500 ppm methane for accurate results from 1-10.000 ppm.
VOCs and Gases Vinyl Chloride MultiRAE/AreaRAE PID

Vinyl Chloride

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Vinyl%20Chloride)

VOCs and Gases

Dräger Tube

Regulatory Info:

TWA:
PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm
IDLH:
NA
AEGL-1 1-hr:
250 ppm
AEGL-1 4-hr:
140 ppm
AEGL-1 8-hr:
70 ppm
PAC-1 15-min (PAC):
250 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
500 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag
Method:
NIOSH 1007/TO 15
Flow Rate/Total Volume:
0.05 L/min; <200mL/min (6L Summa); 0.7-5 L

Dräger Tube

Y 0.5-5 ppm, 5-30 ppm
(Not Applicable)
No 9.99 eV NA 1 ppm = 2.56 mg/m3 III NA NA PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm NA 250 ppm 140 ppm 70 ppm 250 ppm 500 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag NIOSH 1007/TO 15 0.05 L/min; <200mL/min (6L Summa); 0.7-5 L
VOCs and Gases Vinyl Chloride Dräger Tube

Vinyl Chloride

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Vinyl%20Chloride)

VOCs and Gases

Dräger Chip

Regulatory Info:

TWA:
PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm
IDLH:
NA
AEGL-1 1-hr:
250 ppm
AEGL-1 4-hr:
140 ppm
AEGL-1 8-hr:
70 ppm
PAC-1 15-min (PAC):
250 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
500 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag
Method:
NIOSH 1007/TO 15
Flow Rate/Total Volume:
0.05 L/min; <200mL/min (6L Summa); 0.7-5 L

Dräger Chip

Y ≥0.3-10 ppm
(Not Applicable)
No 9.99 eV NA 1 ppm = 2.56 mg/m3 III NA NA PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm NA 250 ppm 140 ppm 70 ppm 250 ppm 500 ppm NA NA Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag NIOSH 1007/TO 15 0.05 L/min; <200mL/min (6L Summa); 0.7-5 L
VOCs and Gases Vinyl Chloride Dräger Chip

Vinyl Chloride

Resources:

  • PubChem (https://pubchem.ncbi.nlm.nih.gov/compound/Vinyl%20Chloride)

VOCs and Gases

TVA 2020

  • TVA 2020 Info (https://www.thermofisher.com/document-connect/document-connect.html?url=https://assets.thermofisher.com/TFS-Assets%2FLSG%2Fmanuals%2FEPM-manual-TVA2020.pdf)
  • (https://www.thermofisher.com/order/catalog/product/TVA2020)
  • Detection Level: 0.5-2,000 ppm (PID); (https://assets.thermofisher.com/TFS-Assets/LSG/manuals/EPM-manual-TVA2020.pdf)
  • Intrinsically Safe: Y (https://www.thermofisher.com/order/catalog/product/TVA2020)
  • Used For Sampling: No
  • 0.5-2,000 ppm (PID);
  • PID CF ISO: 10.6 lamp; 1.281 (10 ppm) - 1.234 (1000 ppm)

Regulatory Info:

TWA:
PEL = 1 ppm, C 5 ppm (15 mins); REL = Ca; TLV = 1 ppm
IDLH:
NA
AEGL-1 1-hr:
250 ppm
AEGL-1 4-hr:
140 ppm
AEGL-1 8-hr:
70 ppm
PAC-1 15-min (PAC):
250 ppm
PAC-1 1-hr:
ERPG-1 1-hr:
500 ppm

Air Sampling:

Media:
Sorbent Tube, Anasorb CSC, 226-01 / Summa Canister / Tedlar Bag
Method:
NIOSH 1007/TO 15
Flow Rate/Total Volume:
0.05 L/min; <200mL/min (6L Summa); 0.7-5 L

TVA 2020

Y 0.5-2,000 ppm (PID);
(https://assets.thermofisher.com/TFS-Assets/LSG/manuals/EPM-manual-TVA2020.pdf)